Free Practice Questions

NHIE Electrical Practice Questions

5 free NHIE electrical practice questions with answers and explanations, covering service equipment, panels, branch circuits, GFCI/AFCI protection and grounding. Written by a Certified Master Inspector.

Home › Free Practice Questions › Electrical

By Gabe Deiro, CMI® · Certified Master Inspector · Updated October 2026

These 5 questions cover service equipment, panels, branch circuits, GFCI/AFCI protection and grounding. On the National Home Inspector Examination they fall under Property Inspection (70% of the exam). Try each one before you open the answer: the explanation matters more than the letter.

1. An inspector observes a 20-amp breaker protecting a circuit wired with 14 AWG copper conductors. This condition should be reported because

  1. 20-amp breakers require aluminum conductors
  2. the breaker should be a GFCI type instead
  3. 14 AWG may be used only for lighting circuits
  4. 14 AWG copper is rated 15 amps and is overfused
Show answer

Answer: D. 14 AWG copper is rated 15 amps and is overfused

14 AWG copper is the minimum branch-circuit conductor and is rated for 15 amps. Protecting it with a 20-amp breaker allows the conductor to carry more current than it can safely dissipate, creating an overheating and fire hazard. This is overfusing, a common panel defect.

Memory tip: 14 gets 15. 12 gets 20.

2. At the main service panel, the inspector finds no bonding jumper connecting the neutral bar to the enclosure. The MOST significant implication is

  1. a ground fault may lack a path to trip the breaker
  2. the panel will not accept any additional breakers
  3. the neutral conductors will carry excess voltage
  4. the panel cannot be grounded to the water pipe
Show answer

Answer: A. a ground fault may lack a path to trip the breaker

At the service equipment, the neutral must be bonded to the enclosure and the grounding system so a fault to the metal enclosure has a low-impedance path back to the source, allowing enough current to trip the overcurrent device. Without it, a faulted enclosure can remain energized.

Memory tip: Bonding gives faults a way home.

3. An older home has a main panel with no single main breaker; four large breakers at the top shut off all power. This arrangement is

  1. a deficiency because a single main disconnect is always required
  2. a deficiency because at most two disconnects are allowed
  3. acceptable under the historic six-handle rule
  4. acceptable only if the breakers are handle-tied
Show answer

Answer: C. acceptable under the historic six-handle rule

Historically, service equipment could use up to six switches or breakers (the “six-handle rule”) to disconnect all power. Newer standards require a single main disconnect for new installations, but existing six-handle panels are not defects by themselves; the inspector should describe the arrangement.

Memory tip: Six throws of the hand, historically.

4. Inside a panel, the inspector finds a conductor with white insulation re-identified with black tape and landed on a breaker. This indicates

  1. an improper connection that must be corrected
  2. a white conductor re-identified as hot, which is permitted
  3. a neutral conductor that has been overloaded
  4. a conductor from a multiwire branch circuit
Show answer

Answer: B. a white conductor re-identified as hot, which is permitted

A white or gray conductor in a cable may be used as an ungrounded (hot) conductor if it is permanently re-identified at each termination, typically with black or red tape or paint. This is common with switch loops and 240-volt circuits and is not a deficiency when properly marked.

Memory tip: White with tape = hot on purpose.

5. A home receives power through conductors that run underground from a utility transformer to the meter. The inspector should describe this as a

  1. service lateral
  2. service drop
  3. feeder
  4. branch circuit
Show answer

Answer: A. service lateral

Underground service conductors from the utility to the meter are a service lateral; overhead conductors from the pole are a service drop. Describing the service type and location is part of reporting system characteristics, and laterals cannot be inspected for most of their length.

Memory tip: Lateral is low; drop is from above.